RTI Technologies, Inc.

February 5, 1996

Page 9

... NOTE

...

Several audible changes may be heard during the recovery and recycling
process.

Refrigerant flow through check valves causes a "sizzle-type" sound.

These changing "noises" are normal and nothing to be concerned about.

The TC670 will automatically recover and recycle refrigerant from the A/C System until a
vacuum is sensed. This vacuum level can be seen on the Low Side Gauge.

!

!

!

! DO NOT TURN THE TC670 OFF OR DISCONNECT HOSES !

!

!

!

A small quantity of Liquid refrigerant will probably still remain in the A/C System. This can
be detected by observing an increasing pressure reading on the Low Side Gauge.

As pressure increases to a preset level, the TC670 will automatically cycle on and off to
continue recovering refrigerant.

Allow this automatic sequence to repeat until the vacuum level remains constant for at least 2
minutes.

5.

Close Red and Blue Hose Valves.

6.

Close High and Low Gauge Valves.

7.

Press bottom (OFF) of rocker switch marked RECOVER/RECYCLE.

PURGE REQUIRED OR CYLINDER FULL LIGHT:

This Light will illuminate if either...

1)

The Charging Cylinder has filled to capacity: Go to Page 13

OR

2)

Pressure on the Purge Gauge approaches 250 psig: Go to Page 10