Oil drain & air purge – MAHLE RTI TC670V User Manual

Page 13

Advertising
background image

RTI Technologies, Inc.

February 5, 1996

Page 10

0

F

R12

R134a

30

42

40

32

44

42

34

46

44

36

48

46

38

50

49

40

52

51

42

54

54

44

57

56

46

59

59

48

61

61

50

64

64

52

66

67

54

69

70

56

72

72

58

74

76

60

77

78

62

80

82

64

83

85

66

85

88

68

88

92

70

92

95

72

95

97

74

98

104

76

102

107

78

105

110

80

108

114

82

112

118

84

115

123

86

118

127

88

123

130

90

127

135

92

130

140

94

135

145

96

138

148

98

143

153

100

147

157

102

150

163

104

155

167

106

160

173

108

165

180

110

168

185

112

173

190

114

178

195

116

183

200

118

188

207

Purge Chart

OIL DRAIN & AIR PURGE

Oil and Non-condensable Gas (Air) are separated from
the recovered refrigerant and MUST be removed
following EACH recycling procedure as follows:

1.

MOMENTARILY turn the Purge Valve (To the
right of the Purge Chart) clockwise and hold until
the pressure reading on the Pressure Gauge above
this valve drops one small graduation mark
(approximately 10 PSIG).

2.

SLOWLY open the Oil Drain Valve (Lower left
side on back of TC670) to vent Non-condensable
Gas and drain any oil which may have been
removed from the A/C System. A plastic cup is
provided to collect the oil.

Unless the A/C System had previously been
overfilled, the TC670 will typically not remove
more than a tablespoon of oil, making replenishment
unnecessary.

Leave the Oil Drain Valve open.

3.

Determine the room temperature.

4.

Locate the pressure (PSIG) corresponding to this
room temperature (

0

F) in the chart on the top of the

TC670. This chart is reproduced at the right.

If the pressure indicated on the gauge is greater than
that determined from the chart...

SLOWLY turn clockwise and hold open the
Purge Valve until the gauge pressure equals that
shown in the chart. Any Non-condensable Gas
will be vented through the Oil Drain Valve.

5.

Close the Oil Drain Valve.

6.

Turn the N/C Vent Valve clockwise and hold for
approximately 5 seconds. This permits any residual
Non-condensable Gas to be recirculated for
reprocessing during the next recycle procedure.