Start-up – Mammoth V-Cube Slim E-Series (Standard Versions) User Manual

Page 10

Advertising
background image

10

MAMM-VCS-IOM-1EB (October 2011)

1. Open all valves to the full open position and turn on

power to the V-Cube Slim™.

2. Set room temperature sensor for “Fan Only” opera-

tion by selecting “Off” at the system switch and
“On” at the fan switch. If “Auto” fan operation is se-
lected, the fan will cycle with the compressor.
Check for proper air delivery.

3. A 5 minute anti-short cycle delay is inherent to the

unit’s microprocessor board. After the 5 minute
delay, check the discharge air temperature using
the unit keypad.

4. Measure the temperature difference between en-

tering and leaving water. The difference in water
temperature should be approximately 1 ½ times
greater in the cooling mode as compared to the
heating mode . Adjust the combination shutoff/
balancing valve in the return line to a water flow
rate which will result in the temperature difference.

5. In the heating mode, with the entering water tem-

perature in the range of 60°F to 80°F, the tempera-
ture difference between the entering water and
leaving water should be between 6°F to 12°F. In
the cooling mode, if the leaving air temperature
falls below 35°F, adjust water flow to the unit to >3
gpm/ton to avoid freeze damage to the unit.

Start-up

6. To verify proper drainage of condensate, slowly

add water to the condensate pan until proper drain-
age is accomplished.

7. If the unit fails to operate, check the following:

8. If the unit starts but after a short time trips on high

or low head pressure, check the following:

a. Verify that the incoming power to the unit

matches the nameplate and that the main dis-
connect is turned on.

b. Verify a call for heating or cooling is present.

a. Verify that airflow is not impeded by a dirty air

filter, improper fan rotation or improper duct
sizing.

b. Verify that the water flow rate is within limits.

Check the water flow balance and back flush if
necessary.

Advertising