Operating limits, Environment – Mammoth V-Cube Slim E-Series (Standard Versions) User Manual
Page 11
11
MAMM-VCS-IOM-1EB (October 2011)
Operating Limits
APPLICATION LIMITS
WATER TEMPERATURES / Degrees F *
Standard range
Low Temp Geothermal
COOLING
HEATING
COOLING
HEATING
MINIMUM ENTERING FLUID TEMPERATURE
50˚
50˚
40˚
25˚
MAXIMUM ENTERING FLUID TEMPERATURE
110˚
90˚
110˚
90˚
* Application limits apply at or above standard flow rates specified for size of unit.
APPLICATION LIMITS
AIR TEMPERATURES / Degrees F *
Standard range
Low Temp Geothermal
COOLING
HEATING
COOLING
HEATING
MINIMUM AMBIENT AIR TEMPERATURE **
50˚
50˚
50˚
50˚
MAXIMUM AMBIENT AIR TEMPERATURE **
110˚
110˚
110˚
110˚
MINIMUM ENTERING AIR TEMPERATURE
65˚
50˚
65˚
40˚
MAXIMUM ENTERING AIR TEMPERATURE
100˚
80˚
100˚
80˚
* Application limits apply at or above standard flow rates specified for size of unit.
** Minimum and maximum ambient conditions apply to ducted supply and return units only.
Environment
This equipment is designed for indoor installation only.
Sheltered locations such as attics, garages, etc., gen-
erally will not provide sufficient protection against ex-
tremes in temperature and/or humidity, and equipment
performance, reliability, and service life may be ad-
versely affected.
Standard range water source heat pump units
Units are designed to start-up in an ambient of 50°F (10°C), with
entering air at 50°F (10°C), with entering fluid at 70°F (21°C), with
both air and fluid flow rates used in the ISO 13256-1 rating test, for
initial start-up in winter. Note that this is not a normal or continuous
operating condition. It is assumed that such a start-up is for the pur-
pose of bringing the building space up to occupancy temperature.
Geothermal range water source heat pump units
Geothermal heat pump units are designed to start-up in an ambient
of 40°F (5°C), with entering air at 40°F (5°C), with entering fluid at
25°F (-4°C), with both air and fluid at flow rates used in the ISO
13256-1 rating test, for initial start-up in winter. Note that this is not a
normal or continuous operating condition. It is assumed that such a
start-up is for the purpose of bringing the building space up to occu-
pancy temperature.
Operating voltages
208-230/60/3 . . . . . . . . . . . . . . . . . . . . 197 volts min.; 253 volts max.
460/60/3 . . . . . . . . . . . . . . . . . . . . . . . . 414 volts min.; 506 volts max.
380-415/50/3. . . . . . . . . . . . . . . . . . . . ..342 volts min.; 418 volts max
575/60/3. . . . . . . . . . . . . . . . . . . . . . . . .515 volts min.; 632 volts max.
Additional Information For Water Source Heat Pump Units Only
Note:
Units operating with over- and under-voltage conditions
for extended periods of time will experience premature
component failure. Three phase system imbalance
should not exceed 2%.