Mammoth epic™ systems, I/o flex 6126 – Mammoth V-Cube Slim E-Series (Standard Versions) User Manual

Page 12

Advertising
background image

12

MAMM-VCS-IOM-1EB (October 2011)

Mammoth EPiC™ Systems

I/O Flex 6126

The standard factory-integrated DDC controller pro-
vides control flexibility that can be easily customized to
meet any sequence of operation needs. It is fully capa-
ble of operating in a 100% stand-alone mode or can
connect to a Building Automation System (BAS) using
any of today’s four leading protocols: BACnet, Modbus,
N2, and Lontalk. The base controller provides 12 in-
puts and 12 outputs plus supports the 8160 expander
module if additional inputs/outputs are required.

Key Features and Benefits

 6160 I/O points: 6 digital outputs, 12 universal inputs, and 6 analog outputs.

 8160 I/O points: 16 universal inputs, 8 digital outputs.

 Optional built-in protocol support: BACnet® (ARCNET, MS/TP, and PTP modes), Modbus® (RTU and ASCII

modes supported), N2, or Lontalk®.


 Powerful, high-speed 16-bit microprocessor with 1 MB Flash memory and 1 MB of battery-backed RAM

 Built-in support through an Rnet port for control’s custom configurable keypad/display unit, BACview6 (4-line by

40 character per line display) for intelligent sensors.


 For variable air volume (VAV), constant volume (CAV), and make-up air (MAU) applications.

Advertising