I/O Zone 583 (RHT, CAV, NMUA) - Examples of I/O’s

Options are in italics. Common options are bolded.

* Cost add option must be ordered to get multiplexing board
** Requires DC relay for single stage, UCS for multi-stage, or actuator for modulating control
*** A minimum of one keypad display must be ordered per project to set required set-points
**** A protocol will be a cost add option

Universal

Input

Jumper Setting

1

Supply Air Temperature (Monitor Only)

Thermistor/Dry Contact

2

Condenser Leaving Water Temperature

Thermistor/Dry Contact

3

Condenser Entering Water Temperature

Thermistor/Dry Contact

4

Cooling Coil Leaving Air Temperature Sensor

Thermistor/Dry Contact

5

Thermistor/Dry Contact

6

Load Shead*

Comp #1Q HP-5 Alarm*

Comp r#2Q HP-5Alarm

Thermistor/Dry Contact

7

Compr Lckt/Overflow

Comp #1 HP-5 Alarm

Comp #2 Alarm

Thermistor/Dry Contact

8

Emergency Shut Down External Clock (Start)

Dirty Filter (Switch Opt)

Thermistor/Dry Contact

Space or Return Humidity

Rnet

Jumper Setting

1

Room/Return Air Temperature (RS Std) or
Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)

N/A

Analog

Output

Jumper Setting

N/A

1

Reheat**

0-10VDC

2

Water Side Economizer** 0-10VDC

3

Auxiliary Heat**

0-10VDC

Analog

Output

Jumper Setting

N/A

1

Supply Fan Start

Dry Contact for 24 VAC

2

Compressor Call #1

Dry Contact for 24 VAC

3

Compressor Call #2

Dry Contact for 24 VAC

4

Reversing Valve

Dry Contact for 24 VAC

5

Common Alarm

Dry Contact for 24 VAC