Mounting

Vertical units can be mounted on the floor or a concrete
pad, typically in a mechanical closet or other area en-
closed from the space to promote a quieter occupied
environment..

Horizontal units must be hung from the ceiling. Mount-
ing brackets, rubber grommets, bolts and washers are

shipped in place on the unit. The mounting brackets
are designed to accept up to a 3/8-inch threaded rod
(by others). A flat washer and two nuts (both by others)
should be used to mount the unit on the ceiling at-
tached threaded rods. When installed, the unit should
be slightly pitched toward the condensate drain con-
nection.

Horizontal mounting detail (See unit submittal drawing for specific component locations on your unit)

3/4” OD Copper Condensate Drain

Water Inlet FPT

Access to Compressor

Water Coil, Reversing Valve

Hanger

Brackets (4)

Electrical

Flange on Filter Guide

Filter, Left or Tight Side
Removal. Lift and Pull on

Flange on Filter Guide

7/8” or 1-3/32” Hole for line
voltage conduit connection

Water Outlet FPT

Connection

Threaded Rod

(By Others)

Washer (by others) must cover

entire bottom of grommet

Retaining nut

(by others)

Note: Rotate Brackets

90° And Tighten

Hanger Bracket

Grommet detail