Mammoth controls – Mammoth 5 to 40 Tons: Water-to-Water (K-Vintage) User Manual
Page 10
10
MAMM-WSHP-IOM-1KA (September 2011)
MAMMOTH CONTROLS
HP 5 Microprocessor Control Board
The standard HP 5 microprocessor control board
provides complete control of a compressor, reversing
valve and offers numerous safety features and
troubleshooting fault indicators. The HP 5 unit is
designed to operate with Mammoth’s existing series of
wall thermostats and arrives factory-installed and wired.
Operation and maintenance (OM) instructions for the
HP 5 control board are contained in a separate
document (MAMM-WSHP-IOM-1HP5). This document
is available on the Mammoth website at
www.mammoth-inc.com
under Literature.
Key Features and Benefits
Low and high voltage protection
Check microprocessor at startup – self-diagnostic
Random start time delay from 5 to 35 seconds
Compressor anti-short cycle protection for 300 seconds (5 minutes)
Compressor and reversing valve control
Compressor lockout with selectable intelligent/manual reset
LED status on the board
Lockout alarm signal to the temperature controller in the event of a safety circuit fault
Operable on 50 and 60 cycle power
Emergency shutdown from a field-supplied signal
Unoccupied (night setback and night setup) mode from a field-supplied signal
Dry contact alarm signal for connection of a fault signal to a DDC controller.
Auxiliary dry contact for tie-in of a motorized valve when the compressor is on (or optional compressor status)
Night heating or cooling operation from temperature controller
Override of the unoccupied mode from the temperature controller
Low and high pressure compressor protection
Low pressure bypass with 0, 1, 2 and 3 minute selections