Operating Limits

Environment

Operating voltages
208-230/60/3. . . . . . . . . 187 volts min.; 253 volts max.
460/60/3 . . . . . . . . . . . . 414 volts min.; 506 volts max.
380-415/50/3. . . . . . . . . 342 volts min.; 456 volts max.
575/60/3 . . . . . . . . . . . . 518 volts min.; 632 volts max.
380/60/3 . . . . . . . . . . . . 342 volts min.; 418 volts max.




Additional Information For Initial Start-up Only

This equipment is designed for indoor installation only.
Sheltered locations such as attics, garages, etc., gen-
erally will not provide sufficient protection against ex-

tremes in temperature and/or humidity, and equipment
performance, reliability, and service life may be ad-
versely affected.

Note:

Voltages listed are to show voltage range. However,
units operating with over- or under-voltage conditions
for extended periods of time will experience premature
component failure. Three phase system imbalance
should not exceed 2%.

APPLICATION LIMITS 

Standard range 

Low Temp Geothermal 

COOLING 

HEATING 

COOLING 

HEATING 

MINIMUM ENTERING WATER TEMPERATURE 

50˚  

40˚ 

25˚**  

25˚** 

MAXIMUM ENTERING WATER TEMPERATURE 

110˚ 

110˚ 

110˚ 

110˚ 

*Application limits apply at or above standard flow rates specified for size of unit. 

** Requires glycol in the system 

 

WATER TEMPERATURES /  Degrees F * 