Vfd general purpose application parameters – Mammoth 7 to 24 Tons: High Efficiency, Superior IAQ Twin and Quad Circuit Horizontal and Vertical (M-Vintage) User Manual
Page 16
16
MAMM-WSHP-IOM-1MA (November 2011)
VFD GENERAL PURPOSE APPLICATION PARAMETERS
Parameter Default
Value
Description
Comments
b1-01
1
Reference Source
0 = Digital Operator (Adjust Motor Speed from keypad)
Speed Control Method
1 = Terminals (Speed Pot. / 0 – 10V / 4—20mA)
b1-02
1
Run Source /
0 = Digital Operator (Start/Stop motor from keypad)
Start/Stop Control Method 1 = Terminals (Start/Stop using external contact / switch)
b1-03
1
Stop Method Selection
0 = Ramp to stop (Motor ramps down at stop command)
1 = Coast to stop (Motor freewheels at stop command)
b1-04
0 Reverse
Operation
0 = Allow motor to run in reverse direction
1 = Reverse direction prohibited
C1-01
10.0 sec.
Acceleration Time
The time it takes to ramp up from 0 to maximum motor speed.
C1-02
10.0 sec.
Deceleration Time
The time it takes to ramp down from maximum motor speed to 0.
C6-01
1
Normal / Heavy Duty
0 = Normal Duty (Use for fan and pump applications)
0 = Normal Duty (Use for fan and pump applications)
d1-01
0.00 Hz
Frequency Reference
Frequency setting when speed is set from the keypad.
d2-01
100.0 %
Frequency Upper Limit
Maximum motor speed allowed (e.g. 100 % = Max rpm)
d2-02
0.0 %
Frequency Lower Limit
Minimum motor speed allowed (e.g. 100 % = Max rpm)
E2-01
*
Motor Rated Current
Motor nameplate current
L1-01
1
Motor Overload Selection
0 = Disabled
1 = Standard Fan Cooled Motor
2 = Standard Blower Cooled Motor
3 = Vector Duty Motor
L1-02
1.0 min
Motor Overload Time
Sets the motor thermal overload protection time.