Vfd general purpose application parameters – Mammoth 7 to 24 Tons: High Efficiency, Superior IAQ Twin and Quad Circuit Horizontal and Vertical (M-Vintage) User Manual

Page 16

Advertising
background image

16

MAMM-WSHP-IOM-1MA (November 2011)

VFD GENERAL PURPOSE APPLICATION PARAMETERS

Parameter Default

Value

Description

Comments

b1-01

1

Reference Source

0 = Digital Operator (Adjust Motor Speed from keypad)

Speed Control Method

1 = Terminals (Speed Pot. / 0 – 10V / 4—20mA)

b1-02

1

Run Source /

0 = Digital Operator (Start/Stop motor from keypad)

Start/Stop Control Method 1 = Terminals (Start/Stop using external contact / switch)

b1-03

1

Stop Method Selection

0 = Ramp to stop (Motor ramps down at stop command)

1 = Coast to stop (Motor freewheels at stop command)

b1-04

0 Reverse

Operation

0 = Allow motor to run in reverse direction

1 = Reverse direction prohibited

C1-01

10.0 sec.

Acceleration Time

The time it takes to ramp up from 0 to maximum motor speed.

C1-02

10.0 sec.

Deceleration Time

The time it takes to ramp down from maximum motor speed to 0.

C6-01

1

Normal / Heavy Duty

0 = Normal Duty (Use for fan and pump applications)

0 = Normal Duty (Use for fan and pump applications)

d1-01

0.00 Hz

Frequency Reference

Frequency setting when speed is set from the keypad.

d2-01

100.0 %

Frequency Upper Limit

Maximum motor speed allowed (e.g. 100 % = Max rpm)

d2-02

0.0 %

Frequency Lower Limit

Minimum motor speed allowed (e.g. 100 % = Max rpm)

E2-01

*

Motor Rated Current

Motor nameplate current

L1-01

1

Motor Overload Selection

0 = Disabled

1 = Standard Fan Cooled Motor

2 = Standard Blower Cooled Motor

3 = Vector Duty Motor

L1-02

1.0 min

Motor Overload Time

Sets the motor thermal overload protection time.