9. Operate the unit configuration menu “EOL Reset”, to reset the ionic bed life. All the

accumulated ionic bed time has been reset to zero. The unit should now be heard filling.

NOTE: The accumulated ionic bed time can be reset to zero at anytime. However, the unit

should not be reset without first inspecting the ionic beds.

10. After the unit has heated up and started making steam, turn main power off and double check tank

access panel gasket for steam leakage. Hand tighten wing nuts or reposition gasket if necessary.

Cleaning the Water Level Electrodes

1. If there is water in the steam generating tank, operate menu to “MANUAL DRAIN”. The drain valve

should energize, and the unit should completely drain.

2. After the tank has drained, turn off the main

power at the disconnect.

3. Unclamp and remove the 5/8” ID Silicone tubing

from the top outlet of the level canister.

4. Disconnect wires #21 (high level probe), #20

(low level probe) and #19 (common probe) from

the probes, noting the probe and wire locations.

Note: Level control float switches are used

for DI, RO, or very pure water. Cleaning

should not typically be required.

5. Unscrew the probes from the level canister

using the hex nut fitting on the probe

(Note: Level canister bushings may be removed with the probes, if necessary).

6. Use a wire brush, wire wheel, or similar means to clean scale deposits off the stainless steel tip of

the probe. Cleaning of the Teflon insulating jacket (white portion) should not be needed.

7. Wipe probes with a clean dry cloth.

8. Inspect the interior of the level canister. If large amounts of scale or debris are present, remove the

canister from the cabinet by removing the two clamping bracket screws and disconnecting the 5/8”

ID Silicone hose at the bottom of the canister. Flush the canister with water to remove debris

and reinstall.

9. Reinstall the probes and probe wires in their proper locations. The high water probe (shortest)

goes in the right hole of the canister. The low water probe (medium length) goes in the left front

hole of the canister. The common probe (longest) goes in the left, rear hole of the canister.

10. Reconnect the 5/8” ID Silicone hose(s).