Table 51-1 modbus variable lists – Armstrong World Industries 6100 User Manual

Page 51

Advertising
background image

51

Table 51-1 Modbus Variable Lists

address description

Value / (unit)

function number Data Class

10001

Fill valve status

0:off 1:on

10002

Drain valve status

0:off 1:on

10003

contactor 1 status

0:off 1:on

10004

contactor 2 status

0:off 1:on

10005

contactor 3 status

0:off 1:on

10006

contactor 4 status

0:off 1:on

10008

Network control

0:Local 1:Remote

1

comm type

0:485 1:PSP

2

Sensor select

0:Humidistat 1:RH sensor

3

High limit sensor select

0:not use 1:use

4

Outside temperature

0:not use 1:use

5

Network enable

0:disable 1:enable

6

Modulating Fill enable

0:enable 1:disable

30001

Desired RH / Demand

(%)

30002

Steam Output

(kg/hr)

30003

Water level

0:low 1:normal 2:high 3:exception

30004

Run status

0:Idle 1:Steam gen. 2:Cycle drain 3:End of season drain 4:Bed dring 5:Failure 6:Drain 7:heat
8:Manual drain 9:Fill 10: Test 11: Manual stop 12: Empty drain

30005

Bed life

(hours)

30006

Bed life

(Minutes)

30007

Run Time

(hours)

30008

Run Time

(Minutes)

30009

Drain Freq

(hours)

30010

Drain Freq

(Minutes)

30011

Idle Time

(hours)

30012

Idle Time

(Minutes)

30013

RH / Demand (Analog input)

(%)

30014

Duct value

(%)

30015

Outside temperature

(

℃)

30016

Water temperature

(

℃)

30017

Heat temperature

(

℃)

30018

Failure

1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit
have reached 100% of bed life 5:Fill time out to low level 6:Water level dropped below level
during normal run 7:Fill time out from low to high level 8:Water level above high level time out
9:Water level has not dropped below low level during an emptydrain 10:End of bed dring

30019

Contactor number

1,2,3,4

30020

Heating Element Power

0:1000W 1:3000 2:5000W 3:6650W 4:8000W

40001

Language Select

0:English 1:Chinese

40002

Set RH / Demand

(%)

40003

Duct High Limit set point

(%)

40004

Outside temp. high set point

(

℃)

40005

Outside temp. low set point

(

℃)

40006

Outside RH low set point

(%)

40007

Run mode

0:Steam Gen 1:Manual Drain 2:Manual Fill 3:Unit stop

40008

AQUASTAT

(

℃)

40009

Bed Life

0:500hours 1:750hours 2:1000hours 3:1250hours 4:1500hours 5:1750hours 6:2000hours
7:2250hours 8:2500hours 9:3000hours 10:No bed

40010

Drain Cycle

0:6hours 1:12hours 2:24hours 3:48hours 4:96hours 5:Real time drain

40011

Drain duration

0:1Minutes 1:5Minutes 2:10Minutes

40012

Signal type

0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA

40013

PID_DIV

40014

PID_PB

40015

PID_SI

(second)

40016

PID_DG

40017

Modulating Fill Cycle

(second)

40018

Modulating Fill duration

(second)

40019

Water temp. compensate

(

℃)

40020

Themocouple compensate

(

℃)

40021

First run

40022

Idle time

(hour) test for End of seanson drain

40023

Drain time

(hour) test for Cycle drain

40024

Bed life

(hour) test for End of Life

40025

Bed drying time

(hour) test for whole Bed drying cycles, 96 hours max.

40026

Bed drying time

(minute) test for one Bed Drying cycle, 30 minutes max.

Modbus Variants list

BI

Bits

AI

AV

function 2 , read

only

function 1,read only

: function 5,15

write

function4 , read

only

function3 read

only,function 6,16

write

function 6 , for

debug only

AV