Installation

(for qualified installers only)

Travis Industries

4 1 2 2 1 0 4

9 3 5 0 8 1 1 7

Vent Requirements

!

Always maintain the required 1” clearance (air space) to combustible materials to prevent a fire hazard.
Do not fill air spaces with insulation.

!

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it’s own separate vent system.

•

This appliance is equipped only for
altitudes 0-2000 feet. However, our
in-house testing has shown that the
unit operated at altitudes to 8000 ft.

!

Failure to adjust the air shutter
properly may lead to improper
combustion which can create a safety
hazard. Consult your dealer or
installer if you suspect an improperly
adjusted air shutter.

•

When the vent passes through a wall,
a wall thimble is required. When the
vent passes through a ceiling, a
support box or firestop is required.
When the vent passes through the
roof, a roof flashing and storm collar
are required. Follow the instructions
provided with the vent for installing
these items.

Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)

Vertical Termination
(Duravent Part # 991)

Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)

8-5/8"

Use a support box
on exposed vent

Vertical Vent

Requirements

Use a wall thimble
whenever passing
through a wall
(Duravent Part #942)

Horizontal Termination
(Duravent Part #984)

Maintain a minimum 1" clearance
from vent to any combustible
(vent is 6 5/8" diameter)

Minimum
Framing for
wall thimble

Horizontal Vent

Requirements

Minimum framing
for fire stop

8-5/8"

Maintain a minimum 1"
clearance from vent to
any combustible (vent
is 6 5/8" diameter)

•

Use one of the following 6-5/8" diameter co-axial gas direct vent systems:

Manuafacturer

S e r i e s

Simpson Dura-Vent

Model GS

Selkirk Hearth Products

Direct-Temp

American Metal Products

Ameri-Vent

N O T E

: Always use the high-wind cap for the type of vent you are using (if applicable)

•

Slide the vent sections together and turn 1/4 turn until the sections lock in place.

•

Screws are not required to secure the vent. However, three screws may be used to
secure vent sections together if desired.

•

High temperature sealant is recommended at the appliance starter section connection
(use high-temperature silicone or Mill-Pac®).

•

If disassembly is required, at time of re-assembly check to see if the vent creates a tight
fit. If it does not, apply high temperature sealant to the joints of the affected sections.

•

Horizontal sections require a 1/4" rise every 12" of travel

•

Horizontal sections require non-combustible support every three feet (e.g.: plumbing
tape)