Hired-Hand System 1000 Power Vent User Manual
Page 17

System 1000 Power Vent
System 1000 Power Vent
Offset and Differential
Offset and Differential
••
14
14
If the Target Temp is set at 80 degrees, Offset at 4 degrees and
Differential set at 2 degrees, The System will disengage Heat Mode
when building temperature reaches 76 degrees.
Example:
Target Temp
-
Offset
=
Heat Mode Off
80
-
4
=
76
Cool Mode:
If the Target Temp is set at 80 degrees, Offset set at 5 degrees, and
Differential set at 2 degrees, The System will engage the fans when
building temperature reaches 87 degrees.
Example: Target Temp +
Offset
+
Differential
=
Cool Mode On
80
+
5
+
2
=
87
If the Target Temp equals 80 degrees, Offset equals 5 degrees, and
Differential equals 2 degrees, The System will disengage the fans when
building temperature reaches 85 degrees.
Target Temp
+
Offset
=
Cool Mode Off
Example:
80
+
5
=
85