Part No. 4801-5124 rev 10-03

Farm Hand Vent Master 24

6

For example, if the Timer Pct. is set for 30, and the timer cycle is set for 10 minutes, the
timed stages will run for 3 minutes out of every 10 minutes (i.e. 30% of the timer cycle).

Runtime Percentage
The Timer Pct. parameter sets the Runtime percentage of all stages that are placed on a
timer (See Section 9.2). The value of the Timer Pct. in the main display refers to a
Runtime % which can be set to values between 5 and 100 using the "+" and "-" buttons.











Target Temperature

The target temperature is the temperature the system tries to maintain.

To adjust these settings, press the mode button until you see the setting you want to
adjust, then use the + button to raise the value, and the - button to lower the value.
When you are finished setting a new value, either press the mode button again, or do
nothing, and the system will return to normal operation within a few seconds.

Target Static Pressure

The Static Pressure the system tries to maintain within the limits of the Pressure
Differential.


To adjust the Target Static Pressure, press the mode button until you see the setting
you want to adjust, then use the + button to raise the value, and the - button to lower
the value. When you are finished setting a new value, either press the mode button
again, or do nothing, and the system will return to normal operation within a few
seconds.

The Pressure Differential is the range around the Target Pressure that is considered
satisfactory. From the Target Pressure and the Pressure Differential the target high
and low pressure limits are calculated as follows:


Target High Pressure Limit = Target Pressure + ½ Pressure Differential

Target Low Pressure Limit = Target Pressure + ½ Pressure Differential

Vent Master 24

(Parameter selection sequence)

Room

Temperature

(Stages 1/12

ON Point)

Static

Pressure

Target

Temperature

Timer

Percentage

Target

Pressure

Room

Temperature
(Stages13/24

On Point)

For Target Temperature, both

the Target LED and the

Temperature LED will be

lighted.

For Target Pressure, both the

Target LED and the Static

Pressure LED will be lighted.