Installation – Lincoln Electric IM589 INVERTEC V250-S User Manual

Page 10

Advertising
background image

A-3

INSTALLATION

INVERTEC V250-S

A-3

POWER INPUT CONNECTION FOR 50/60 HZ
MACHINES

1. Connect terminal marked to earth ground

per National Electric Code.

2. Connect the supply lines to the line switch. Torque

to 3.0 Nm.

3. Install in accordance with all local and national

electric codes.

The Invertec V250-S 50/60 Hz machine is supplied
with one cord connector. The cord connector provides
a strain relief for the input power cord as it passes it
through the rear access hole. The cord connector is
designed for a cord diameter of 7.9 to 27.2mm (.310
to 1.070 in).

Strip away outer jacket of cord, trim fillers and insert
conductors through cord connector. The jacketed por-
tion of the cord must go through the cord connector.
Tighten both connector screws.

INPUT FUSE AND SUPPLY WIRE

Refer to the

Technical Specifications page at the

beginning of this chapter for the proper fuse sizes and
supply cable sizes.

• Fuse the input circuit with recommended super lag

fuses or delay type circuit breakers.

• Install the proper fuse in the fuse holder in the main

disconnect panel.