Installation, Premises wiring, Circuit breakers – Lincoln Electric IM973 OUTBACK 145 User Manual

Page 13: Caution plugs and hand held equipment, Auxiliary power receptacles, Warning

Advertising
background image

A-6

INSTALLATION

OUTBACK™ 145

A-6

®

PREMISES WIRING

The OUTBACK™ 145 is not recommended for
premises wiring. The OUTBACK™ 145 does not have
a combined 120/240 volt receptacle and cannot be
connected to a premises.

The OUTBACK™ 145 is intended only for backup
intermittent power.

Certain electrical devices cannot be provided by the
OUTBACK™ 145. Refer to table A.2 for these
devices.

CIRCUIT BREAKERS

Auxiliary power is protected by circuit breakers. When
the machine is operated in high temperature environ-
ments, the breakers may tend to trip at lower loads
than normally.

NEVER BYPASS THE CIRCUIT BREAKERS. WITH-

OUT OVERLOAD PROTECTION, THE UNIT COULD

OVERHEAT AND/OR CAUSE DAMAGE TO THE

EQUIPMENT BEING USED.

------------------------------------------------------------------------

CAUTION

PLUGS AND HAND HELD EQUIPMENT

For further protection against electric shock, any elec-
trical equipment connected to the generator recepta-
cles must use a three-blade, grounded type plug or an
Underwriterʼs Laboratories (UL) approved double
insulated tool with a two blade plug.

Never operate this machine with damaged or
defective cords. All electrical equipment must be
in safe operating condition.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The control panel of the OUTBACK™ 145 features
three auxiliary power receptacles:

• Two 20 amp,120 volt duplex (double outlet)

receptacle.

• A 50 amp, 240 volt single outlet receptacle.

See Figure A.1

Through these receptacles the machine can supply up
to 4750 watts peak or 4250 watts continuous of sin-
gle-phase 60 Hertz AC power. The machine output
voltages meet UL standards and fall within ± 10% of
the rated voltage.

WARNING

Advertising