Control Panel

3. INSTALLATION

DANGER:

All wiring should be done by a certified technician or electrician to ensure

adherence to the applicable electrical safety wiring regulations and installation codes.

Failure to follow these instructions can damage the unit and could also result in personal

injury or loss of life.

CAUTION:

Before beginning unit installation, please consider the following:

The unit should be used or stored in an indoor area away from direct sunlight, heat, moisture

or conductive contaminants.

When placing the unit, allow a minimum of three inches of space around the unit for optimal

ventilation.

Preparing for Installation

Before you begin the installation, be sure to review the Important Safety Instruction on page 3 of

this manual and be aware of all safety and electrical codes which must be met in your area.

AC Input of the inverter charger can be supplied from either a split-phase or a dual-input AC

Source. See below to understand more about the unit before you start your installation.

Input AC Source from Split-Phase:

The split-phase AC source has 2 lines, 1 neutral and 1 ground. The two 120Vac lines are 180

degree out of phase with each other with a total of 240Vac when measured from line to line. The

voltage between each line to neutral is 120Vac.

Input AC Source from Dual Input:

The dual input has 2 line inputs, 1 neutral and 1 ground. The two 120Vac lines are in phase and

must come from the same source.

AC Loads:

In Battery-Inverter mode, the unit’s AC Output L1 and L2 lines are connected together to provide

120Vac on both lines.

In Pass-Through mode, the AC source connected to the unit’s AC input is passed through to the

AC Output (load).

DANGER:

Electrical Shock Hazard. Do not connect 240VAC load to the AC Output of the unit.

AC Output Neutral Bonding:

Each AC source must have its neutral conductor bonded to ground.

When the Nature Power Inverter-Charger is running in Battery-Inverter mode, the internal

neutral-to-ground bonding system is enabled. The unit will act as an AC source and will

automatically connect the AC Output Neutral (N1 & N2) circuit to safety ground.

When the unit is running in Pass-Through mode, the internal neutral-to-ground bonding system

is disabled. The unit will not act as an AC source and the AC Output (N1 & N2) to safety ground

is disconnected inside the unit. Therefore, the AC Input source that is connected to the Inverter-

Charger should have its own neutral-to-ground connection. If not, have an electrician look into

bonding the AC source’s neutral to ground at your AC source.

Reset button

Power button

Status LED

Indicator

Fan opening

DC Input

Terminal +

Ventilation

DC Input

Terminal -

GND Stud