Installation – Star Water Systems S1503 User Manual

Page 4

Advertising
background image

4

© Copyright 2013 Star Water Systems. All Rights Reserved.

STEP 4: (Continued)

4.2) Do not braze/solder copper fittings within 18” of Home Guard

®

Optima, as the heat from the torch will damage

the pump body.

4.3) When assembling threaded fittings into the Home Guard

®

Optima inlet, do not use pipe dope on the inlet threads,

use PTFE (Teflon

®

) sealing tape. Take special care to keep any debris (including pieces of tape) from entering

the inlet fitting that might get caught in the operating valve.

4.4) The Home Guard

®

Optima includes a field installed Push-to-Connect fitting. This fitting is designed to be used

with ¾” PEX, CPVC, or copper pipe. The fitting must be installed on the ¾" NPT thread of the pump inlet fitting.

Caution must be used when installing the fitting to not over tighten the inlet fitting and crack the body. Using a

backup wrench, hold the inlet fitting while tightening the Push-to-Connect fitting. If the Push-to-Connect fitting

is not used, the same precaution must be used when installing any other fitting to the inlet fitting.

4.5) Purge the water line prior to connecting to the Home Guard

®

Optima to ensure that debris does not enter the unit

and clog the operating valve.

4.6) If using the Push-to-Connect fitting, cut the tube so that the ends are square. Ensure that there are no burrs or

damage to the cut end. Once the tubing end is cut square and clean, scribe a depth mark on the outside of the

tubing 1” from the end. Insert the tube through the release collar to rest against the grab ring. Push the tube

firmly with a slight twisting action until it reaches the tube stop. The depth mark should be up to the end of the

release collar. The tube liner is not necessary with CPVC or Copper tubing, and may be removed based on

preference or local codes. The tube liner can be easily removed by pulling it out with a needle nosed pliers.

4.7) Once the pump has been installed and the municipal water source connected, open the municipal water source

valve and the supply line valve. Inspect the valve body and all connections looking for leaks. Close the

municipal water valve and fix any leaks before operating the pump.

STEP 5: Testing of Pump Operation

5.1) Unplug the primary pump so that it does not start.

5.2) Fill the sump with water until the Home Guard

®

Optima starts.

5.3) Verify that the pump starts and stops at the desired ON/OFF points.

5.4) Verify that there are no leaks in the discharge line.

5.5) If adjustment is necessary, raise or lower the stops according to STEP 2.

5.6) If the pump is not operating properly after following the above steps, refer to the Troubleshooting guide.

5.7) When finished testing, plug primary pump back into AC receptacle.

WATER PRESSURE:

20 PSI minimum with valve open.

80 PSI maximum with valve open.

100 PSI maximum with valve closed.

EFFICIENCY:

The pumping capacity increases with household water pressure and flow.

At an eight-foot static head and a supply pressure of 20 PSI at water supply inlet with water flowing, it takes one (1)

gallon of supply water to remove one gallon from the sump. As the supply pressure increases with the static head

constant, less supply water is required.

Installation (

Continued

)

Advertising