Model TP-524D

TP-524D Instruction Manual

Rev. 0.5

Page 9 of 36

NOTE 3: The supply of power should be from an isolated source with over-current protection
as stipulated in table.

NOTE 4: A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used.

Terminal Connections

CAUTION: Do not apply System power to the sensor until all wiring is properly terminated. Refer to

Section 2.7 Initial Start Up

Customer

Wiring

White

Blue

Yellow

Black

Wiring to

H2S Sensor

Figure 9 Sensor Connector PCB

a) Remove the junction box cover and unplug the Transmitter Module. Identify the terminal blocks for

customer wire connections.

b) Observing correct polarity, terminate the 3-conductor 4-20mA field wiring (DC+, DC-, and MA) to the

sensor assembly wiring in accordance with the detail shown in Figure 9.

c) Trim all exposed wire leads if they are not permanently landed in the terminal block.

d) Plug the Transmitter Module into the connector PCB and replace the junction box cover.

NOTE: A 6-32 or 8-32 threaded exterior ground point is provided on most junction boxes for
an external ground. If the Sensor Assembly is not mechanically grounded, an external ground
strap must be used to ensure that the sensor is electrically grounded.

2.7 Initial Start Up

Upon completion of all mechanical mounting and termination of all field wiring, apply system power 24VDC
(typical) and observe the following normal conditions:

a) TP-524D display reads “0”, and no fault messages are flashing.

b) A temporary upscale reading may occur as the sensor heats up. This upscale reading will decrease to “0”

ppm within 1-2 minutes of power-up, assuming there is no gas in the area of the sensor.

NOTE: The 4-20mA signal is held constant at 4mA for the first two minutes after power up.

c) Remove the desiccant cap about 10 minutes after applying power to the sensor and install the

weatherproof splashguard accessory supplied with the sensor.