Model TP-524D

TP-524D Instruction Manual

Rev. 0.5

Page 32 of 36

8. Appendix

8.1 Specifications

Sensor Type:

Continuous diffusion/adsorption type
CHEMFET Solid State MOS type

Sensor Life:

5-10 years typical

Measuring Ranges:

0-20ppm, 0-50ppm, or 0-100ppm

Accuracy/ Repeatability:

± 2ppm or ±10% of applied gas (whichever is greater)

Response/clearing Time:

T50 < 30 seconds, T80 < 60 seconds

Outputs:

Linear 4-20mA DC

Electrical Classification:

Explosion Proof
CSA and US (NRTL)

Class I, Division 1, Groups B, C, D (Tamb= -40°C to 75°C)
Class I, Zone 1, Group IIB+H2

FM Approvals

Class I, Division 1, Groups B, C, D (Tamb= -40ºC ≤ Ta ≤ 60ºC)

ATEX

EExd IIB+H2 T4 (Tamb= -40ºC ≤ Ta ≤ 60ºC)

Performance Approvals:

ISA 92.0.01 Part I-1998;
H2S Performance Requirements

Safety Approvals:

C

CSA

US

CSA/NRTL (US OSHA Certified)

FM

ATEX
CW Marking

Ingress Protection:

NEMA 4X, IP66

Applicable Standards

CSA C22.2 No. 30-M1986
CSA C22.2 No. 142-M1987
UL No. 916
UL No.1203
FM 3810
FM 3600
FM 3615
FM 6340

Warranty:

Electronics – 2 years
Sensor – 10 year conditional

Environmental Specifications

Operating Temperature:

-40°C to +75°C (-40°F to +167°F)

Storage Temperature:

-35°C to +55°C (-31°F to +131°F)