Edwards Signaling 2400 Series User Manual
Page 25

17
Table 5.2 - Programming Step Indications
Program Step
Power LED Flash Phase
Module Placement & Verification
1 =
Y
PAUSE
Y
PAUSE
Y
...
Initiating Device Circuits (IDC)
2 =
YY
PAUSE
YY
PAUSE
YY
..
Indicating Appliance Circuits (IAC)
3 =
YYY
PAUSE
YYY
PAUSE
YYY
..
Timer Settings
4 =
YYYY
PAUSE
YYYY
PAUSE
YYYY
..
Auxiliary Power Setting
5 =
YYYYY
PAUSE
YYYYY
PAUSE
YYYYY
..
To modify the panel default settings shown in Table 5.1, enter the programming mode as follows:
1.
Move the
PROGRAMMING MODE
switch to the ON (down) position.
2.
Press the
RESET
switch. The green Power LED will display a single-phase flash after approximately 20
seconds. The trouble buzzer sounds at a four pulse/minute rate, indicating you are in the automatic
module placement & verification step of the programming process.
The panel automatically identifies all option modules installed in the panel by lighting each installed
module's amber trouble LED. This process can take up to 30 seconds. Failure to light a module’s
trouble LED indicates a defective module or connection.
NOTE
If no front panel switches are activated for 15 minutes after entering the programming
mode, the panel automatically exits the programming mode. The trouble buzzer will
remain active as long as the
PROGRAMMING MODE
switch is in the ON (programming)
position.
5.1 Programming Initiating Device Circuits (IDCs)
1.
Press the
RESET
switch to enter the Initiating Device Circuit configuration step. The program IDC step
is indicated by the 2-phase flashing green Power LED. IDC zones are programmed individually,
starting with zone #1. The IDC zone actively being programmed is identified by an active zone LED.
The IDC circuit type may be identified by the LED color and flash rate, using Table 5.3.
Table 5.3 - IDC Zone Type Codes
IDC Zone Type
Zone LED Code
Alarm, Non-Verified Detector
Steady Red
Alarm, Verified Detector & Dry Contact Alarm Initiating
Devices. (Do NOT select this option. High Impedance
Detectors are not presently available.)
Y
PAUSE
Y
PAUSE
Y
... RED
Alarm, Verified Detector ONLY
For Low Impedance devices only.
(ex. 2400 series detectors)
No contact devices permitted.
YY
PAUSE
YY
PAUSE
YYY
.. RED
Normally-Open Supervisory
Steady Amber
Waterflow
Steady Green
Waterflow with Retard
Y
PAUSE
Y
PAUSE
Y
... GREEN