Edwards Signaling 2400 Series User Manual

Page 25

Advertising
background image

17

Table 5.2 - Programming Step Indications

Program Step

Power LED Flash Phase

Module Placement & Verification

1 =

Y

PAUSE

Y

PAUSE

Y

...

Initiating Device Circuits (IDC)

2 =

YY

PAUSE

YY

PAUSE

YY

..

Indicating Appliance Circuits (IAC)

3 =

YYY

PAUSE

YYY

PAUSE

YYY

..

Timer Settings

4 =

YYYY

PAUSE

YYYY

PAUSE

YYYY

..

Auxiliary Power Setting

5 =

YYYYY

PAUSE

YYYYY

PAUSE

YYYYY

..

To modify the panel default settings shown in Table 5.1, enter the programming mode as follows:

1.

Move the

PROGRAMMING MODE

switch to the ON (down) position.

2.

Press the

RESET

switch. The green Power LED will display a single-phase flash after approximately 20

seconds. The trouble buzzer sounds at a four pulse/minute rate, indicating you are in the automatic
module placement & verification step of the programming process.

The panel automatically identifies all option modules installed in the panel by lighting each installed
module's amber trouble LED. This process can take up to 30 seconds. Failure to light a module’s
trouble LED indicates a defective module or connection.

NOTE

If no front panel switches are activated for 15 minutes after entering the programming

mode, the panel automatically exits the programming mode. The trouble buzzer will

remain active as long as the

PROGRAMMING MODE

switch is in the ON (programming)

position.

5.1 Programming Initiating Device Circuits (IDCs)

1.

Press the

RESET

switch to enter the Initiating Device Circuit configuration step. The program IDC step

is indicated by the 2-phase flashing green Power LED. IDC zones are programmed individually,
starting with zone #1. The IDC zone actively being programmed is identified by an active zone LED.
The IDC circuit type may be identified by the LED color and flash rate, using Table 5.3.

Table 5.3 - IDC Zone Type Codes

IDC Zone Type

Zone LED Code

Alarm, Non-Verified Detector

Steady Red

Alarm, Verified Detector & Dry Contact Alarm Initiating
Devices. (Do NOT select this option. High Impedance
Detectors are not presently available.)

Y

PAUSE

Y

PAUSE

Y

... RED

Alarm, Verified Detector ONLY
For Low Impedance devices only.
(ex. 2400 series detectors)
No contact devices permitted.

YY

PAUSE

YY

PAUSE

YYY

.. RED

Normally-Open Supervisory

Steady Amber

Waterflow

Steady Green

Waterflow with Retard

Y

PAUSE

Y

PAUSE

Y

... GREEN