Edwards Signaling 2400 Series User Manual
Page 46

38
Table 10.2 - 60 Hours Supervisory, 5 Minutes of Alarm
Signal Circuit Alarm Current for 5 Minutes
Aux. Circuit Current: 0-0.5 Amps for 5 Minutes
Panel Current Load
Signal Circuit Alarm Current (A)
Aux. Sup
Current
#
Zones
#
Option
Modules
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0 mA
Amp/Hour Battery Size
“
2
0
4.5
4.5
4.5
4.5
4.5
6.5
6.5
6.5
“
2
1
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
“
2
2
6.5
6.5
6.5
8.0*
8.0*
8.0*
8.0*
8.0*
“
2
3
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
“
4
0
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
“
4
1
6.5
6.5
6.5
8.0*
8.0*
8.0*
8.0*
8.0*
“
4
2
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
“
8
0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
25 mA
Amp/Hour Battery Size
“
2
0
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
“
2
1
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
“
2
2
8.0*
-
-
-
-
-
-
-
4
0
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
4
1
8.0*
-
-
-
-
-
-
-
50 mA
Amp/Hour Battery Size
“
2
0
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
8.0*
-
* = Must Purchase Auxiliary Battery Box P/N 2400-BATBOX Separately.