Remote annunciator modules- front view – Edwards Signaling 2400 Series User Manual
Page 74

[EALZRTU.CDR]
1. IF
USING 4-WIRE SMOKE
DETECTOR, CONFIGURE
AUXILIARY POWER AS
NON-RESETTABLE.
NOT
2. REFER TO BATTERY
CALCULATION SECTION FOR
POWER REQUIREMENTS.
3. ALL WIRING POWER LIMITED.
CONTACTS SHOWN IN
NORMAL CONDITION.
4
6
7
5
8
9
9
10
10
POSITIVE ANNUNCIATOR
POWER WIRING:
LED ANNUNCIATOR WIRING:
SUPERVISED FOR OPENS AND
GROUND FAULTS.
NOT SUPERVISED.
24VDC NOMINAL @
15mA DC MAX. PER CIRCUIT.
24VDC NOMINAL
@ 500mA DC MAX
18 AWG MIN.=7,500’ (2,300 M) MAX.
22 AWG MIN.=3,000’ (900 M) MAX.
22 AWG MIN.=7,500’ (2,300 M) MAX.
NOTES
ANNUNCIATOR COMPONENT SELECTION GUIDE
IDC TO ANNUNCIATOR DRIVER CORRELATION
MODE
ACTIVE IDC ZONE
ACTIVATED
ANNUNCIATOR DRIVER
MASTER (-ADM)
OUTPUT
ACTIVATED
ANNUNCIATOR DRIVER
SLAVE (-ADS)
OUTPUT
1
1
2
2
3
3
4
4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BASE PANEL IDC ZONE #1
BASE PANEL IDC ZONE #2
1st IDC MODULE, ZONE #1
1st IDC MODULE, ZONE #2
2nd IDC MODULE, ZONE #1
2nd IDC MODULE, ZONE #2
3rd IDC MODULE, ZONE #1
3rd IDC MODULE, ZONE #2
PANEL OPTION
MODULE(S)
ANNUNCIATOR
HARDWARE
ANNUNCIATOR
MOUNTING
TROUBLE ONLY
TROUBLE &
4 ALARM ZONES
TROUBLE &
8 ALARM ZONES
4 ALARM
ZONES ONLY
8 ALARM
ZONES ONLY
NONE
RTU
1 GANG BOX
2 x1 GANG BOX
2 GANG BOX
2 x1 GANG BOX
2 GANG BOX
3 x1 GANG BOX
3 GANG BOX
1 GANG BOX
RTU & 4ZA
RTU4ZA
RTU & 2 x 4ZA
RTU8ZA
ANNUNCIATOR
DRIVER MASTER
ANNUNCIATOR
DRIVER MASTER
ANNUNCIATOR
DRIVER MASTER
& SLAVE
ANNUNCIATOR
DRIVER MASTER
& SLAVE
4ZA
2 x 4ZA
8ZA
REMOTE ANNUNCIATOR MODULES- FRONT VIEW
RTU
RTU4ZA
4ZA
RTU8ZA
8ZA
TB1
TB1
TB1
1
1
2
2
3
3
4
4
+
+
+
+
+
+
NC NO
AUX
ALARM
TROUBLE
SIG1
SIG2
INP1
INP2
PGM
MODE
+
+
+
+
+
CONTROL PANEL
4
6
7
7
9
9
6
6
8
5
1
1
2
2
3
3
4
4
RTU
4ZA
4ZA
ANNUNCIATOR DRIVER SLAVE
ADS
INSTALLED ON BACK OF
ANNUNCIATOR DRIVER MASTER
ANNUNCIATOR DRIVER MASTER
ADM
INSTALLED IN PANEL
WIRE
JUMPER
NO CONNECTION
1
1
1
2
2
2
3
3
3
4
4
4
REMOVE JUMPER TO ENABLE
CORRESPONDING ZONE LED
REMOVE JUMPER TO ENABLE
CORRESPONDING ZONE LED
9
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
POWER ON
NORMAL
SILENCE
SYSTEM
TROUBLE
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
POWER ON
POWER ON
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
NORMAL
NORMAL
SILENCE
SILENCE
SYSTEM
TROUBLE
SYSTEM
TROUBLE