Section 1: product description, 1 product features, Product features – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 10

Advertising
background image

10

411UDAC Manual — P/N 51073:E 9/20/2013

Section 1: Product Description

The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines.
The four inputs use conventional input devices. The 411UDAC accepts waterflow devices, four-
wire smoke detectors, pull stations and other normally-open contact devices. The unit also super-
vises AC voltage, telephone line input voltage/current, battery level and battery charger operation.

Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable
Form-C relays and 12 VDC resettable special application power. The 411UDAC interfaces with
the public switched telephone network and is compatible with most central station receivers. A
total of fifteen popular communications formats are supported, including the industry standard
Ademco Contact ID. The communicator also contains a unique DACT option that eliminates
'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a
24 hour period.

Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the
PK-411UD Windows

®

-based remote site programming software. The 411UDAC is supplied with

a compact metal cabinet.

The digital communicator can be programmed or interrogated off-site via the public switched tele-
phone network. Any IBM compatible personal computer with Windows

®

XP or greater, with a

1200 baud Hayes

®

compatible modem and Upload/Download software P/N PK-411UD, may serve

as a service terminal.

1.1 Product Features

•

Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)

•

Programmable input channels

4-wire smoke (Inputs 1 & 3 only)

pull station

normally-open contact

host panel trouble (Slave Mode)

supervisory

supervisory autoresettable

waterflow (silenceable)

waterflow (nonsilenceable)

•

One Style Y (Class B) NAC (supplementary application)

•

Dual telephone lines

Dual telephone line voltage detect

Alternating phone lines for 24 hour test messages

•

12 VDC operation

•

Alarm Verification

•

Signal Silence Inhibit

•

Autosilence

•

Trouble Reminder

•

Trouble Resound - troubles will resound the buzzer every 24 hours at midnight until the
trouble is cleared

•

Optional TR-6 Series Trim Ring

•

20-digit central station and service terminal telephone numbers

•

NAC coding per ANSI S-3.41 (Temporal Coding)

Figure 1.1 411UDAC Digital

Communicator

41

1uda

cv.wmf

Advertising