411UDAC Manual — P/N 51073:E 9/20/2013

Product Description

Controls and Indicators

1.4 Controls and Indicators

Front Panel Switch

•

Reset Switch - to reset 411UDAC circuits

•

Acknowledge/System Silence Switch
– press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and

change all flashing LEDs to steady on)

– press a second time and hold for minimum of two seconds to perform a System Signal

Silence (silence Notification Appliance Circuit)

411UDAC Piezo Sounder

•

The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT
troubles include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone
number 1 or 2 communication fault and total communication failure. Separate and distinct
sounds are provided for the following conditions:

alarm - steady On

trouble - 1 second On and 1 second Off

supervisory - ½ second On and ½ second Off

Front Panel Indicator

•

AC Power - green LED

•

Input Active - red LED

•

Communication Fail - yellow LED

•

System Trouble - yellow LED

•

Supervisory - yellow LED

•

Battery Trouble - yellow LED

Circuit Board Indicator

•

Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)

Figure 1.2 411UDAC Controls and Indicators