Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 68

Advertising
background image

68

411UDAC Manual — P/N 51073:E 9/20/2013

Programming Sheets

Digital Communicator Options Program Sheet (Factory Defaults)

A.2 Digital Communicator Options Program Sheet (Factory

Defaults)

To enter Programming Mode, press the MODE key, 7764, and then the [ENTER/STORE] key.

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.

20

Primary Central Station Communication Format: 'E' for Ademco Contact ID Format.

21

22

23

24

Primary Central Station Account Code.

25

26

27

28

Primary Central Station 24-hour Test Time: '0000' = 12:00 midnight.

29

Primary Number Test Time Interval. '0' for 24-hours.

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.

50

Secondary Central Station Communication Format: 'E' for Ademco Contact ID Format..

51

52

53

54

Secondary Central Station Account Code:

55

56

57

58

Secondary Central Station 24-hour Test Time: '0000' = 12:00 midnight.

59

Secondary Number Test Time Interval. '0' for 24-hours.

60

AC Loss Reporting Delay. '2' for 2 hour delay.

61

Backup Reporting. '0' to report to Secondary phone number as backup only.

62

Reserved for Future Use.

63

DACT Trouble Reminder. '0' disables trouble reminder.

64

Operational Mode Selection. '0' enables stand-alone mode, disables communication to Central Station.

65

Input Channel 1 Function Selection. '0' for fire alarm.

66

Input Channel 2 Function Selection. '1' for pull station alarm.

67

Input Channel 3 Function Selection. '0' for fire alarm.

68

Input Channel 4 Function Selection. '1' for pull station alarm.

69

70

71

Input Channel 1 Delay Timer. '000' for no delay. Does not delay fire functions.

72

73

74

Input Channel 2 Delay Timer. '000' for no delay. Does not delay fire functions.

75

76

77

Input Channel 3 Delay Timer. '000' for no delay. Does not delay fire functions.

78

79

80

Input Channel 4 Delay Timer. '000' for no delay. Does not delay fire functions.

81

Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.

82

Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.

83

Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.

84

Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio.

85

Output Relay #1 enable. '0' to disable relay.

86

Output Relay #1 Function. '0' for activatation on fire alarm (4-wire smoke).

87

Output Relay #2 enable. '0' to disable relay.

88

Output Relay #2 Function. '2' for activation on DACT trouble.

F F F F F F F F F F F F F F F F F F F F

0 0 0 0

E

0

0 0 0 0

F F F F F F F F F F F F F F F F F F F F

0 0 0 0

E

0 0 0 0

0

2

0

0

0

0

0

1

1

0

0 0 0

0 0 0

0 0 0

0 0 0

0

0

0

0

0

0

0

2