4 auxiliary dc power output connections, 5 input/initiating circuits, 1 cmd inputs – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 32: Auxiliary dc power output connections, Input/initiating circuits, Cmd inputs

Advertising
background image

32

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

Auxiliary DC Power Output Connections

2.4 Auxiliary DC Power Output Connections

The Special Application Auxiliary DC power output is power-limited (Class 2).

2.5 Input/Initiating Circuits

2.5.1 CMD Inputs

The ECC-50/100 has eight Command Input circuits, which are used to activate the panel amplifiers

which, in turn, transmit an audio signal over the system speakers. All field wiring for the circuits is

power-limited (Class 2) and supervised for opens and ground faults. Note that zero impedance to

ground will cause a ground fault.
CMD1 and CMD2 Command Input circuits can be independently field programmed to be triggered

by a contact closure or by the reverse polarity of a Notification Appliance Circuit.
IMPORTANT! When CMD1 and CMD2 are configured for reverse polarity, the NAC cannot be
Coded (including NAC Sync).

CMD1 has internal relay contacts before the out terminals which will open the outgoing NAC cir-

cuit during an ECC-50/100 trouble condition (AC loss is programmable as described in Section 3).

This causes a NAC trouble at the host FACP. Note that CMD1 and CMD2 configurations can be

independently set so that both circuits are triggered by the same type of input or by different types

of inputs (see Figure 2.9 below).

TB17

Special Application Power (500 mA @ 24 VDC) is nonresettable power suitable

for powering control modules and End-of Line Power supervision relays.

See Device Compatibility Document for compatible devices.

Figure 2.8 Auxiliary Power Connection

e

c

c

tb

1

7

.w

m

f

Figure 2.9 Command Input Circuits

Style Z (Class A)

FACP ELR
(for Style Y - Class B only)

NAC reverse polarity trigger
(alarm polarity shown)

Class B (Style B) Contact Closure trigger input, such as
an emergency signaling manual pull station (MNS only).
(4.7K, 1/2 watt EOL Resistors P/N: 71252)

ECC-50/100 Main Control Board

e

c

c

tb

4

.w

m

f

alarm polarities shown

Host FACP

NAC

TB4

CMD1

TB5

CMD2

TB6

CMD3,4

TB7

CMD5,6

TB8

CMD7,8

Advertising
This manual is related to the following products: