Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 17

Advertising
background image

Document #50801 Rev. C 12/14/01 P/N 50801:C

17

Optional Accessories

LDM Series Lamp Driver Modules (Graphic Annunciator)

The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander mod-
ules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power
and control for a maximum of three expander modules (expander modules are not required when interfacing to the
MS-2410BC). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and
input connectors which are used for remote switch functions. The LDM Series requires the use of the LED-10IM
Interface Module. Refer to the LDM Series Lamp Driver Modules Manual for a complete description.

LDM-32F - The Lamp Driver Module has 32

alarm lamp/LED driver outputs which sink cur-
rent to system common (-) on activation. A sin-
gle positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all
drivers are activated. The LDM-32F provides a
separate driver for system trouble and inputs for a
local lamp test switch. A maximum of 16 exter-
nal control switches may be wired to the
LDM-32F. DIP switch SW3 is used to enable or
disable the onboard piezo sounder, enable remote
switch functions, select a flashing LED function
for new alarms and troubles and other functions.
Switch SW4 is used to configure the module to
annunciate 32 alarms or 16 alarms and 16 trou-
bles. A green ON-LINE LED flashes to indicate
ongoing communications with the host FACP.
One LDM-32F supports up to three LDM-E32F
modules. The LDM-32F is supplied with four
standoffs and screws for mounting to a CHS-4L
chassis or custom backbox.

FCPS-24F Remote Power Supply (System Power Expansion)

The FCPS-24F is a compact, remote power supply and battery charger. This remote power supply consists of a fil-
tered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits (four Class B or
two Class A and two Class B). Alternately, the four Notification Appliance Circuits may be used as auxiliary
power configured for resettable or nonresettable operation.

The FCPS-24F may be used in a number of different applications. It may be used as a remotely mounted power
supply and battery charger powering up to four, coded or noncoded, Notification Appliance Circuits. Alternately,
any or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors
or any device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs
to expand FACP auxiliary system power.

FIGURE 1-13:

LDM-32F Module

FIGURE 1-14:

FCPS-24F

Class B/Class A Notification Appli-

ance Circuit or 24 VDC Output #1

Class B Notification Appliance

Circuit or 24 VDC Output #2

Class B/Class A Notification Appli-

ance Circuit or 24 VDC Output #3

Class B Notification Appliance

Circuit or 24 VDC Output #4

Battery Charger

FCPS Trouble

Contact Output

Specific Application

Power

AC Power

Notification Appliance Circuit

Control Input #1 (from FACP)

Notification Appliance Circuit

Control Input #2 (from FACP)

Advertising