Program Features and Options

LDMs, LED-10 series and ACM-8RFs, be certain that none of the other devices are set to address 01. For proper
supervision of all annunciators, only one AFM series annunciator (fixed at address '01') should be installed.

Trouble Reminder

The Trouble Reminder feature provides an audible reminder that an alarm or trouble still exists on the FACP after
the control panel has been silenced. The factory default for this feature is 'disabled'. When this feature is 'enabled',
the control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a
trouble condition, after the Signal Silence or Acknowledge switch is pressed. The piezo will continue to sound at
these rates until the alarm or trouble condition is cleared.

TABLE 3-10:

Annunciator Addressing - Zone 8 Alarm LED

Zone Trouble LED Number (yellow)

Highest Installed Annunciator Address

1

01 - default

2

02

3

03

4

04

5

05

6

06

7

07

8

08

9

09

10

10

TABLE 3-11:

Trouble Reminder - Zone 9 Alarm LED

Zone Trouble LED Number (yellow)

Trouble Reminder

1

Disabled = LED Off (factory default)

Enabled = LED On