Battery Calculations

54

Document #50801 Rev.C 12/14/01 P/N 50801:C

A.1

Main Power Supply

The MS-2410BC provides filtered power for operating the fire alarm control panel, operating external devices and
operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or non-
alarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply.

Be certain to power 4-wire smoke detectors from TB2, Terminals 3 and 4. In Table A-2 , external devices are con-
nected to TB2 only.

TABLE A-2:

Filtered Load in Standby

@24 VDC

.

Device Type

# of

Devices

Current

(amps)

Total Current

(amps)

Main Circuit Board

1

X

0.138

=

0.138

RTB Remote Trouble Buzzer

(1 max.)

X

0.020

=

LED-10IM

(1 max.)

X

0.017

=

4XTMF Module

(1 max.)

X

0.005

=

2-wire Detector Heads

[ ]

X

[ ]

1

1. Refer to the Device Compatibility Document for 2-wire smoke detector standby current.

=

4-wire Detector Heads

[ ]

X

[ ]

1

=

Power Supervision Relays

2

2. Must use compatible listed Power Supervision Relay.

[ ]

X

0.025

=

Current Draw from TB2

(nonalarm

3

)

3. The total standby current must include both the resettable (TB2 Terminals 3 & 4) and nonresettable (TB2

Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified (see Table A-2 ).

=

Sum Column for Standby Load

=