3-1

Section 3
Before You Begin Installing

This section of the manual is intended to help you plan your tasks to facilitate a smooth
installation. Please read this section thoroughly, especially if you are installing a MS-25 panel
for the first time.

3.1

What’s in the Box?

The MS-25 ships with the following hardware:

•

A cabinet with all hardware assembled

•

Two keys for the front door

•

Installation and Operation manual P/N 53688

•

Ten 4.7K ohm end-of-line resistors

•

A battery cable for batteries wired in series

3.2

Environmental Specifications

It is important to protect the MS-25 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:

•

Intended for indoor use in dry locations only

•

Do not mount directly on exterior walls, especially masonry walls (condensation)

•

Do not mount directly on exterior walls below grade (condensation)

•

Protect from plumbing leaks

•

Protect from splash caused by sprinkler system inspection ports

•

Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)

When selecting a location to mount the MS-25 control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.