Model MS-25 Installation and Operation Manual

4-8

53688

Note: The following formulas were used to generate the wire distance chart:

Wiring Distance calculation example:

Suppose a system is configured with the following SBUS modules:

1 - Module MS-25 Fire Annunciator

The total worst case current is calculated as follows:

Using this value, and referring to the Wiring Distance table, it can be found that the available
options are:

1852 feet maximum using 22 Gauge wire

4688 feet maximum using 18 Gauge wire

6000 feet maximum using 16 Gauge wire

6000 feet maximum using 14 Gauge wire

Maximum Resistance (Ohms) =

6.0 Volts

Total Worst Case Current Draw (amps)

Maximum Wire Length (Feet) =
(6000 feet maximum)

Maximum Resistance (Ohms)

* 500

Rpu

where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)

Table 4-2:

Typical Wire Resistance per 1000 ft. using Copper Wire

Wire Gauge

Ohms per 1000 feet (Rpu)

22

16.2

18

6.4

16

4.02

14

2.54

MS-25 Current Draw

= 1 x .04 amps

= .04 amps

Total Worst Case Current Draw

= .04 amps