GW Instek PSP Series User Manual
Page 16

PSP SERIES
USER MANUAL
26
*A
Function:
The present output current, the unit is A.
Syntax:
A<cr> HEX = 41 0D
Explain:
When the message of A<cr>is sent to the power supply from computer,
the power supply will return the following message immediately:
Aa.aaa<cr> 6 characters totally + CR/LF
The contents consist of the uppercase A, the numeral from 0 to 9 and
decimal. Further details is described as follows:
a.aaa = The present output current, the unit: A
*W
Function:
The present output load, the unit is W.
Syntax:
W<cr>
HEX = 57 0D
Explain:
When the message of W<cr>is sent to the power supply from
computer, the power supply will return the following message
immediately:
Wwww.w<cr>
6 characters totally + CR/LF
The contents consist of the uppercase W, the numeral from 0 to 9 and
decimal. Further details is described as follows:
www.w = The present output load, the unit: W
PSP SERIES
USER MANUAL
27
*U
Function:
The maximum voltage limit at present, the unit is V.
Syntax:
U<cr> HEX = 55 0D
Explain:
When the message of U<cr> is sent to the power supply from
computer, the power supply will return the following message
immediately:
Uuu<cr> 3 characters totally + CR/LF
The contents consist of the uppercase U and the numeral from 0 to 9.
Further details is described as follows:
uu = The maximum voltage limit at present, the unit: V
When the uppercase U becoming the lowercase u means that the
power supply is in the setting status of voltage limit mode.
*I
Function:
The maximum current limit at present, the unit is A.
Syntax:
I<cr>
HEX = 49 0D
Explain:
When the message of I<cr>is sent to the power supply from computer,
the power supply will return the following message immediately:
Ii.iii<cr>
5 characters totally + CR/LF