American Dryer Corp. Gas/HSI & Steam ID-120 User Manual

Page 21

Advertising
background image

17

IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust

duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water

column (W.C.).

a. Ducting (Horizontal and Vertical)

1) For single dryer horizontal ducting the minimum duct size is 16-inches (40.64 cm) in diameter, the

duct run should not have more than one (1) elbow (including outside protection), and must not

exceed 40 feet (12.2 meters) in total length. With single dryer vertical ducting, the minimum duct

size is 18-inches (45.72 cm) in diameter, the duct run should not have more than three (3) elbows

(including outside protection), and must not exceed 20 feet (6.1 meters) in total length.

IMPORTANT: When the ductwork approaches the maximum limits as noted in this manual, a

professional heating, venting, and air conditioning (HVAC) firm should be consulted

for proper venting information.

ALL ductwork should be smooth inside with no projections from sheet metal screws or other

obstructions, which will collect lint. When adding ducts, the duct to be added should overlap the

duct to which it is to be connected. ALL ductwork joints must be taped to prevent moisture and

lint from escaping into the building. Inspection doors should be installed at strategic points in the

exhaust ductwork for periodic inspection and cleaning of lint from the ductwork.

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible

materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around).

The duct must be centered within this opening.

Advertising