American Dryer Corp. Gas/HSI & Steam ID-120 User Manual

Page 23

Advertising
background image

19

IMPORTANT: Exhaust back pressure measured by a manometer at each dryer exhaust duct area

must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column

(W.C.).

The duct should be smooth inside with no projections from sheet metal screws or other obstructions,

which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it

is to be connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping

into the building. Inspection doors should be installed at strategic points in the exhaust ductwork

for periodic inspection and cleaning of lint from the ductwork.

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible

materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around).

The duct must be centered within this opening.

b. Outside Ductwork Protection

1) To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the exhaust ductwork travels vertically

up through the roof, it should be protected from the weather by using a 180° turn to point the

opening downward. In either case, allow at least twice the diameter of the duct between the duct

opening and nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust

ductwork.

Advertising