ELECTRICAL CONNECTIONS

22

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Cut off the inner shield (10), the stranded drain wire (6) and the shields of the insulated con-

ductors. Make sure not to damage the stranded drain wires (1, 20, 30).

4 Slide the insulation tubing over the stranded drain wires (1, 20, 30).
5 Crimp the wire end ferrules onto the conductors and stranded drain wires.
6 Pull the heat-shrinkable tubing over the prepared signal cable.

Figure 3-6: Signal cable B, preparation for field housing

a = 80 mm / 3.15"
b = 10 mm / 0.39"