4.4.2 Manufacturer specific parameters of the signal converter for Resource Block

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

DEV_DESCRIPTION

DEV_DESCRIPTION

DEV_DESCRIPTION

DEV_DESCRIPTION

Device Description

Device Description

Device Description

Device Description

R

Describes some characteristics of the device.

-

DB_DEVICE

Data Base GDC

R

Data base version of the GDC device.

Current data base

version

C_NUMBER_DEVICE

C-Number Device

R

Current C-Number of this device.

Current C-Number

Device

C_NUMBER_

PRODUCT

C-Number Production

R

C-Number of production; this number identifies the type of

electronics, can be found on the converter assembly sticker

as well.

Current C-Number

Production

CONVERTER_MODEL

Converter Model

R

The model of signal converter.

MFC300

LOGICAL_PLACE

Logical Place

R

Setting:

Error / Standard / Extended standard / Special

Standard

SUPPLY_OPTION

Supply Option

R

Supply of sensor and electronics option.

Current Supply

Option

Setting:

configuration error / unknown / 100…230 VAC + no option /

100…230 VAC + capacit.Elect. / 100…230 VAC + Virtual Ref /

100…230 VAC + non Ex Adapter / 12…24 VDC + no option /

12…24 VDC capacit.Elect. / 12…24 VDC + Virtual Ref /

12...24 VDC + non Ex Adapter / 24 VAC/DC + no option /

24 VAC/DC + capacit.Elect. / 24 VAC/DC + Virtual Ref /

24 VAC/DC + non Ex Adapter

DISPLAY_OPTION

Display Option

R

Setting:

Configuration error or missing / Standard / Eastern Europe /

Northern Europe / Southern Europe / Far East / Japanese /

Chinese / Russian

as ordered

IO_SELECTION

IO1 Modules IO

R

Setting:

configuration error or missing / no IO selection / Basic IO / Exi

IO: CO act + PO pas / Exi IO: CO pas + PO pas /

Mod. IO: CO act, PO act/high current / Reserved /

Mod. IO: CO act, PO pas/high current /

Mod. IO: CO act, PO pas/Namur /

Mod. IO: CO pas, PO act/high current /

Mod. IO: CO pas, PO pas/high current /

Mod. IO: CO pas, PO pas/Namur / PROFIBUS PA /

Foundation Fieldbus / PROFIBUS DP / RS485 Modbus /

RS485 Modbus with active termination /

CAN Bus BATCHCONTROL /

CAN Bus BATCHCONTROL + outputs /

Foundation

Fieldbus

IO_MODULE_A

IO2 Module Term. A

R

Setting:

configuration error or missing / without carrier /

Exi OPt.: CO act +PO/CI pas / Exi OPt.: CO pas + PO/CI pas /

Exi OPt.2: Currin act + PO/CI pas /

Exi OPt.2: Currin pas + PO/CI pas / Exi OPt.3: 2xCurrin act /

Incl. carrier, without IO module / Current Out act /

Current Out pas / Pulse Out act/high current /

Pulse Out pas/high current / Pulse Out pas/Namur /

Control In act/high current / Control In pas/high current /

Control In act/Namur / Tidalflux / Temperature Input /

Current Input act / Current Input pas

as ordered