The pulse output is a passive "open collector" output which is electrically separated from the
current interface and the measuring sensor. It can be configured as a high current output or
NAMUR output using a jumper on the amplifier board.
The maximum frequency of the pulse output is f
max
= 0.5 Hz
The maximum frequency of the pulse output is f
max
= 0.5 Hz
Jumper in NAMUR setting
Jumper in NAMUR setting
Jumper in NAMUR setting
Jumper in NAMUR setting
R
i
= 900 Ω
U
max
= 36 VDC
Jumper in high current setting
Jumper in high current setting
Jumper in high current setting
Jumper in high current setting
Open:
Maximum voltage U
max
= 36 VDC
Closed current I
R
< 1 mA
Closed:
Maximum current I
max
= 100 mA
Voltage U < 2 VDC
Figure 4-4: Jumper settings pulse output
1 Electronic insert
2 Jumper on board
3 Jumper in high current setting
4 Jumper in NAMUR setting