KROHNE OPTISOUND 3020C 4wire EN User Manual

Page 11

Advertising
background image

1

2

Fig. 3: Min. distance to the max. level

1

Dead zone

2

Reference plane

Information:

If the product reaches the transducer, buildup can form on it

over a period of time and later cause measurement errors.

1

3

2

100%

0%

Fig. 4: Measuring range (operating range) and max. measuring distance

1

full

2

empty (max. measuring distance)

3

Measuring range

Gauge pressure in the vessel does not influence OPTISOUND

3020 C. Low pressure or vacuum, however, damp the

ultrasonic pulses. This influences the measuring result,

particularly if the level is very low. With pressures under -

0.2 bar (-20 kPa) you should use a different measuring

principle, e.g. radar or guided microwave.

Pressure/Vacuum

OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire

11

Mounting

30508

-EN

-050914