Supplementary Documentation BM 70 A, BM 70 P with PROFIBUS-PA


KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5

  D-47058 Duisburg

6/7

Tel.: 0203-301 309 Fax: 0203-301389 · e-mail: [email protected]

Meaning of the status byte (1 Byte):

Quality

Quality-Substatus

Limits

Gr Gr QS QS QS QS Qu Qu
2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

0 0

=

bad

0 1

=

uncertain

1

0

= good (Non Cascade)

1

1

= good (Cascade) - not supported

Status = bad
0

0

0

0

0

0

= non-specific

0

0

0

0

0

1

= configuration error

0

0

0

0

1

0

= not connected

0

0

0

0

1

1

= device failure

0

0

0

1

0

0

= sensor failure

0

0

0

1

0

1

= no communication (last usable value)

0

0

0

1

1

0

= no communication (no usable value)

0

0

0

1

1

1

= out of service

Status = uncertain

0

1

0

0

0

0

= non-specific

0

1

0

0

0

1

= last usable value

0

1

0

0

1

0

= substitute-set

0

1

0

0

1

1

= initial value

0

1

0

1

0

0

= sensor conversion not accurate

0

1

0

1

0

1

= engineering unit violation (unit not in the valid set)

0

1

0

1

1

0

= sub-normal

0 1 0 1 1 1

=

configuration

error

Status = good (Non-Cascade)

1

0

0

0

0

0

= ok

1

0

0

0

0

1

= active block alarm

1

0

0

0

1

0

= active advisory alarm (priority < 8)

1

0

0

0

1

1

= active critical alarm (priority > 8)

1

0

0

1

0

0

= unacknowledged block alarm

1

0

0

1

0

1

= unacknowledged advisory alarm

1

0

0

1

1

0

= unacknowledged critical alarm

1

0

1

0

0

0

= initiate fail safe

1 0 1 0 0 1

=

maintenance

required

Status = Limits

0

0

= ok

0

1

= low limited

1

0

= high limited

1

1

=

constant


Check the first two quality bits in order to get the quality information of the measurement value:
Good (non Cascade) measurement value is ok and can be used without restrictions
Uncertain

measurement value can be used but the accuracy can not be guaranteed (e.g. measurement
value has been frozen or A/D converter is saturated)

Bad

measurement value is bad don´t use it

Good (Cascade)

not supported because it´s not applicable for measurement devices


Diagnostics
If the device has been detected an error additional diagnostic information will be send to the master. The meaning of
the additional information is described within the GSD file under UNIT_DIAG_BIT(i).

 