KROHNE OPTISWITCH 5100C Contactless EN User Manual
Page 28

Screw terminals
for wire cross-section up to 1.5 mm²
(0.0023 in²)
Adjustment elements
Mode switch
- A
Max. detection or overflow/overfill protection
- B
Min. detection or dry run protection
Density switch
- 0.5
0.5 … 2.5 g/cm³ (0.018 … 0.9 oz/in³)
- 0.7
0.7 … 2.5 g/cm³ (0.025 … 0.9 oz/in³)
Voltage supply
Supply voltage
20 … 253 V AC, 50/60 Hz, 20 … 253 V DC
Domestic current requirement
approx. 3 mA (via load circuit)
Load current
- min.
10 mA
- max.
400 mA (with I> 300 mA the ambient temper-
ature can be max. 60 °C) max. 4 A up to 40 ms
(not WHG specified)
Electrical protective measures
Protection
IP 66/IP 67
Overvoltage category
III
Protection class
I
Approvals
1)
ATEX II 1/2G, 2G EExd d IIC T6
2)
Overfill protection acc. to WHG
Ship approvals
1)
Deviating data in Ex applications: see separate safety instructions.
2)
Only with Aluminium housing.
Supplement
28
OPTISWITCH 5100 C, 5150 C - with contactless electronic switch
30428
-EN
-060831