KROHNE OPTISWITCH 5200C Contactless EN User Manual

Page 18

Advertising
background image

SW E60C

2 0 - 2 5 3 V A C / D C

m a x 4 0 0 m A

A

B

L
N

L

N

1 2

0,5 g / cm3

0,7 g / cm3

+

+

1 2

1 2

3

5

1

2

4

Fig. 11: Electronics and connection compartment, single chamber housing

1

Control lamp

2

DIL switch for mode adjustment

3

DIL switch for switching point adaptation

4

Ground terminal

5

Screwed terminals

We recommend connecting OPTISWITCH 5200 C, 5250 C in

such a way that the switching circuit is open when there is a

level signal, line break or failure (safe condition).
The contactless electronic switch is always shown in non-

operative condition.
The instrument is used for direct control of relays, contactors,

magnet valves, warning lights, horns etc. It must not be

operated without an intermediately connected load, because

the electronics would be destroyed if connected directly to the

mains. It is not suitable for connection to low voltage PLC

inputs.
Domestic current is temporarily lowered below 1 mA after

switching off the load so that contactors, whose holding current

is lower than the constant domestic current of the electronics,

are reliably switched off.
When OPTISWITCH 5200 C, 5250 C is used as part of an

overfill protection system acc. to WHG, also note the

regulations of the general type approval.

Electronics and connection

compartment

Wiring plan

18

OPTISWITCH 5200 C, 5250 C - with contactless electronic switch

Connecting to voltage supply

30433

-EN