1 Important information for installation: PLEASE NOTE

•

Location and position as required,
but electrode axis X – • – • – • – X
must be approximately horizontal in a
horizontal pipe run.

Y terminal box or converter housing

•

Measuring tube must be completetly filled at all times.

•

Direction of flow is arbitrary. Arrow on flowmeter can normally be ignored.
For exceptions, refer to Section ”Factory settings” in the installation and operating
instructions for the signal converter.

•

Stud bolts and nuts: to fit, make sure there is sufficient room next to the pipe flanges.

•

Vibration: support the pipeline on both sides of the compact flowmeter.
Level of vibration in conformity with IEC 068-2-34:
20-500 Hz, ran dom / 2 g rms / 30 minutes / x, y, z directions.

•

Do not expose to direct sunlight,
fit a sunshade if necessary, not included with flowmeter, to be provided by customer.

X

X

•

Handling
Do not lift flowmeter by the
signal converter housing or
the terminal box.

Do not set flowmeter down on signal
converter housing or terminal box.

•

Use only solventless detergents to clean the signal converter housing (polycarbonate).

•

Temperatures
For operating pressure and vacuum load based on flange standards, see Section 10
“Technical data“.

Y

Ambient temperature

Process temperature

Compact systems

Standard

-25 to +60 °C (-13 to +140 °F)

-60 to +

0

60 °C (-76 to +140 °F)

-25 to +40 °C (-13 to +104 °F)

-60 to +140 °C (-76 to +284 °F)

EEx-version

-25 to +60 °C (-13 to +140 °F)

-20 to +

1

60 °C (- 4 to +140 °F)

-25 to +40 °C (-13 to +104 °F)

-20 to +140 °C (- 4 to +284 °F)

IFS 5000 F (separate): Standard

-25 to +60 °C (-13 to +140 °F)

-60 to +180 °C (-76 to +356 °F)

EEx version

-25 to +60 °C (-13 to +140 °F)

-20 to +

1

60 °C (- 4 to +140 °F)

-25 to +40 °C (-13 to +104 °F)

-20 to +150 °C (- 4 to +302 °F)