Installation instructions VARIFLUX 6000

1

Important information for installation: PLEASE NOTE !

• Handling


Do not lift flowmeter by the signal converter
housing or the terminal box.

Do not set flowmeter down on signal converter
housing or terminal box.

PLEASE NOTE: the temperature limits for storage and transport, see below.

• Use only solventless detergents to clean the signal converter housing (polycarbonate).

• Temperatures

Refer to Section 11 “Limits” for operating pressure and vacuum load based on flange
standards and type of tube liner.

Ambient temperature

Process temperature

Compact systems

-25 to +60 °C (-13 to +140 °F)

-20 to + 60 °C (-4 to +140 °F)

-25 to +40 °C (-13 to +104 °F)

-20 to +140 °C (-4 to +284 °F)

VARIFLUX 6000

-25 to +60 °C (-13 to +140 °F)

-20 to + 60 °C (-4 to +140 °F)

-25 to +40 °C (-13 to +104 °F)

-20 to +140 °C (-4 to +284 °F)


• Location and position as required,

but electrode axis
X – • – • – • – X
must be approximately horizontal in a horizontal pipe run.

Y terminal box or converter housing

• Measuring tube must be completely filled at all times.

• Direction of flow is arbitrary. Arrow on flowmeter can normally be ignored. For exceptions,

refer to Section “Factory settings” in the installation and operating instructions for the signal
converter.

• Stud bolts and nuts: to fit, make sure there is sufficient room next to the pipe flanges.

• Vibration: support the pipeline on both sides of the compact flowmeter.

Level of vibration in conformity with IEC 068-2-34: 20-500 Hz, random / 2g runs / 30 minutes /
x, y, z directions.

• Do not expose to direct sunlight, fit a sunshade if necessary, not included with flowmeter,

to be provided by customer.