Fct. 3.3.9 Cutoff “off” value for SMU-I
(appears only if “YES” set in fct. 3.3.7).
Range: 02 to 20 PERCENT of Q

100%

.

This value must be greater than that of fct. 3.3.8,
otherwise a “parameter check” error (fct. 4.5.0) will
occur, see sect. 4.2 + 4.3. When the flow returns to the
cutoff “off” value, the current output returns to normal.

Fct. 3.4.6 Low-flow cutoff (SMU) for F desired?
Set NO or YES.

Fct. 3.4.7 Cutoff “on” value for SMU-F
(appears only if “YES” is set in fct. 3.4.6).
Range: 01 to 20 PERCENT of Q

100%

.

The low-flow cutoff drives the frequency output to 0 Hz
when the flow decreases to the cutoff “on” value.

Fct. 3.4.8 Cutoff “off” value for SMU-F
(appears only if “YES” is set in fct. 3.4.6).
Range: 02 to 20 PERCENT of Q

100%

.

T h is valu e m u st be greater th an th at of fct. 3 .4 .7 , oth erw ise a
“ param eter ch eck” error (fct. 4 .6 .0 ) w ill occu r, see sect. 4 .2 +
4 .3 . W h en th e flow retu rn s to th e cu toff “ off” valu e, th e
freq u en cy ou tpu t retu rn s to n orm al.

5.11

F/R operation for I or F

Electrical connection, characteristic and setting of
outputs, refer to sect. 2.3, 5.7 + 5.8.
Fct. 3.1.7 Define direction of forward (normal) flow
(+ or -).
In the case of F/R operation, set the direction of the
forward flow with “+” or “-”, in accordance with the
arrows marked “+” and “-” on the primary head. Note
that if the flowmeter does not have a “+” and “-” on the
primary head the “+” direction is the direction in which
the arrow is pointing. When the low-flow cutoff is active,
it will also operate with the F/R operation.

Fct. 3.1.1 Full-scale setting for flowrate Q

100%

Set the full-scale range. Unit and range, see sect. 5.1 +
5.3.

Fct. 3.1.2 Separate range desired for reverse flow?
Set “YES” only if the range required for reverse flow is
different from the normal (forward) flow. If not, set
“NO”.

Fct. 3.1.3 Full-scale range for reverse flow
(appears only if “YES” is set in fct. 3.1.2).
This is used for setting the full-scale range for reversed
flow. Unit and range, see sect. 5.1 + 5.3. This value must
not be greater than that of fct. 3.1.1, otherwise
“parameter check” error (fct. 4.2.0) will occur, see sect.
4.2 + 4.3.

5.12

Language of display texts

A choice of languages for other display texts is offered in
fct. 3.6.1. The software is equipped with the languages:

GB/USA

English and

D

German or

F

French.

Other languages can be delivered on request.

5.13

Coding desired for entry into setting level?

•

Set NO or YES in fct. 3.6.2.

•

If NO is set, only press the

→

key to get into the

setting mode.

•

If YES is set, press the

→

key and then a 9-keystroke

combination to enter the setting mode.

•

Factory-set Entry Code 1:

→

→

→

↵

↵

↵

↑

↑

↑

•

To change the Entry Code 1:

Select fct. 3.6.2 ENTRY.CODE 1: set YES.
Select fct. 3.6.3 CODE 1 (appears only if YES is set
in fct. 3.6.2). Press the

→

key, displayed:

Code 1 _ _ _ _ _ _ _
Press any 9-keystroke combination. Every keystroke
acknowledged by “*”. Then set the same keystroke
combination again. WRONG CODE (= incorrect
entry) appears if 1

st

and 2

nd

entries are not equal.

Press the

↵

and the

→

keys and repeat settings.

5.14

Behavior of outputs during setting

•

Behaviour of outputs during setting Set in fct. 3.6.5
whether or not the outputs shall hold the last values
(before entry into the setting mode).

•

If “YES” is set: output values prior to entry into the
setting mode are retained during setting. After
leaving the setting mode, the outputs go to the values
corresponding to the actual operating conditions.

•

If “NO” is set: the outputs go to the set minimum
values:

I

to 0/4 mA (see fct. 3.3.2)
or to the value of I

0%

(see fct. 3.3.3).

F

or to 0 V, consequently no pulses.

5.15

User-defined unit

An arbitrary volumetric flow unit or, if density of the
fluid product is consistent and known, a unit of mass
(weight) can be set in fct. 3.6.6 to 3.6.8. The unit “ h
Liter
/hr” (hecto-liters per hour) is factory-set unless
another special unit is specified. US-version: “US
Mgal/DAY
” (US million gallons per day).

Fct. 3.5.6 Text for user-defined unit

•

Volumetric (or mass) unit per unit of time.

•

Text for volume (mass): 6 characters (places).

•

Text for time: 3 characters (places).

•

The fraction bar “/” in the 7

th

place has a fixed

position.

•

Alpha characters A-Z and a-z, numbers 0-9, symbols
+, - or blank character (= underscore) are selectable
for every place.

•

Pressing the

↑

key will sequence the alpha characters

and numbers in the order given above.

•

The

→

key shifts the cursor 1 place to the right.

•

Text examples are given in the following tables in
brackets (...../..).