Supplementary Documentation

Page 11 of 44

IFC090, IFC090 i with FF

IFC090-FF Block Description

IFC090 FF 01/2006

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg

Tel.: 0203-301 309 ‚ Fax: 0203-301389 · E-mail: [email protected]

Parameter

Access

Description

CYCLE_SEL R/W

Used to select the block execution method for this resource. The following methods
are available:

Scheduled

Completion of block execution

see also: CYCLE_TYPE

CYCLE_TYPE R

Identifies the block execution methods available for this resource.

DD_RESOURCE R

It is possible to deliver devices which have the DD for its resource within the device.
This parameter assigns the tag where to find the DD in the resource. Since the
IFC090-FF doesn't come with a 'build-in' DD, this value is blank.

DD_REV R

Revision associated with the DD of the resource – used by interface devices to locate
the DD file for the resource.

DEV_REV R

KROHNE revision number associated with this resource – used by interface devices to
locate the DD file for the resource.

DEV_TYPE R

KROHNE model number of the IFC090-FF – used by interface devices to locate the
DD file for the resource.

FAULT_STATE R

Condition set by loss of communication to an output block.

NOTE:
Since the IFC090-FF doesn’t have an output block, this parameter isn’t supported.

FEATURES R

Used to show supported resource block options. The following features are supported
by the IFC090-FF:

Reports

Soft Write Lock

see also: FEATURE_SEL

FEATURE_SEL R/W

Used to select supported features. The following features are selectable:

Reports

enable sending of alert reports

Soft Write Lock

enable soft write locking of parameters

see also: FEATURE_SEL

FREE_TIME R

Available time for configuration of further blocks.
NOTE:
Since the IFC090 blocks are preconfigured, this value is always zero (0).

FREE_SPACE R

Available memory for configuration of further blocks.
NOTE:
Since the IFC090 blocks are preconfigured, this value is always zero (0).

GRANT_DENY R/W

Options for controlling access of host computer and local control panels to operating,
tuning and alarm parameters of the block.

NOTE:
This parameter is not supported by IFC090-FF

HARD_TYPES R

The type available input signal that is delivered by the Transducer Block and used as
Analog Input Block input parameter. For the IFC090-FF this is ‘Scalar Input’ (1).

ITK_VER R

Major revision number of the interoperability test case used in certifying this device as
interoperable.

NOTE:
Due to an error, this value is ‘0’, but has to be ‘4’ (since the IFC090-FF is interoperable
with interoperability test case version 4).

LIM_NOTIFY R/W

Maximum number of unconfirmed alert notifies messages allowed. This number
always has to be less than MAX_NOTIFY.

see also: MAX_NOTIFY