The a.m. setpoint TOTAL_SP can be set by user to an arbitrary value and is writable in every Integrator Block

operation mode. It defines the reset or starting points for the Up- and Down-integration types.

RESET_IN and OP_CMD_INT can be used to initiate an operator controlled reset. While RESET_IN is an input

parameter, which can be linked to any discrete output parameter of another block, OP_CMT_INT is a contained

parameter, which only can be changed by a direct write.

For the Periodic integration type, it is necessary to define a time, the totalization is being reset. CLOCK_PER is

the parameter referenced for this time and interpreted as value with unit seconds. The user can set this

parameter to any arbitrary value.

5.4.6 Integrator

Reset

Strategies

Depending on the chosen type of Integration (see 5.4.5), the integrators support different kinds of reseting the

totalization (i.e. the value of output parameter OUT). In the following, possible reset strategies are described

subject to the integration type:

Up auto

There are two kinds of reset possible:

• Automatic Reset

Reference point is the value of TOTAL_SP. If the totalization, i.e. the OUT value, exceeds TOTAL_SP, it is

reset to zero (0.0). A snapshot of the value at which the reset happened is saved in parameter STOTAL6.

• Operator

Reset

No integrator internal reference point is used, but an input signal coming from another block or the operator.

By writing ‘reset’ to parameter OP_CMT_INT, the operator is able to reset the totalization at any point in

time.

If the operator wants to define a control strategy for resetting the totalization, it can use the input parameter

RESET_IN. Connecting this parameter with a different block’s discrete output parameter makes is possible

to reset the totalization by sending a value not equal to zero (0) via this connection.

Up demand

Only one kind of reset is possible: Operator Reset. See ‘Up auto‘ above for details.

Down auto

Similar two Up auto, two kinds of reset are possible:

• Automatic Reset

Reference point is 0.0. If the totalization, i.e. the OUT value, falls below 0.0, it is reset to TOTAL_SP. A

snapshot of the value at which the reset happened is saved in parameter STOTAL7.

• Operator

Reset

See ‘Up auto’, ‘Operator Reset’ for details.

6

This could be useful, since normally the totalization isn’t reset exactly with the value of TOTAL_SP, but with a value with an additional

amount of measurement quantity.

7

This could be useful, since normally the totalization isn’t reset exactly with the value of TOTAL_SP, but with a value with an additional

amount of measurement quantity.