Use a regular pattern to tighten the bolts evenly
3.4.5 Maximum pipework forces (end loadings)
Mass flowmeters have a maximum level of force (negative or positive) that can be applied to the
ends of the meter. Refer to the table below for permitted forces.
Maximum end loadings
• These (axial) loads have been calculated, based on 316L schedule 40 process pipework,
where un-radiographed butt welds have been used in pipe joints.
• The loads shown are the maximum permitted static load. If loads are cycling (between
tension and compression) these loads should be reduced. For advice, consult the
manufacturer.
S15
S25
S40
S50
Flanges
Flanges
Flanges
Flanges
20°C
40 barg
25kN
38kN
48kN
99kN
100 barg
17kN
19kN
15kN
20kN
130°C
32 barg
18kN
28kN
35kN
72kN
80 barg
12kN
12kN
7kN
8kN
Hygienic (all connections)
Hygienic (all connections)
Hygienic (all connections)
Hygienic (all connections)
130°C
10 barg
5kN
9kN
12kN
12kN