5/1

5 Description of functions

π

4

π

4

5.1 Full-scale range Q

100%

Fct. 1.01 FULL SCALE
Press

key.

Choice of unit for full-scale range Q

100%

m3/hr

(cubic metres per hour)

Liter/Sec

(litres per second)

US.Gal/min

(US gallons per minute)

User-defined unit, factory-set is „Liter/hr“ (litres per hour) or “US MGal/day”, see Sect. 5.13.

Select with

key.

Use

key to transfer to numerical setting, 1st number (cursor) flashes.

Set full-scale range Q

100%

The setting range is dependent on meter size (DN) and flow velocity (v).

Q

min

= DN

2

x v

min

Q

max

= DN

2

x v

max

(refer to flow table in Sect. 10.1)

0.0053

33 929

m

3

/hr

0.00147

9 424.5

Liter/Sec

0.00233

– 151 778

US.Gal/min

Change flashing number (cursor) with

key.

Use

key to shift cursor 1 place to right.

Press

key to return to Fct. 1.01 FULL SCALE.

Note if “VALUE P” is displayed after pressing

key:

PULSE/VOL. is set under Fct. 1.06 PULS B1, subfunction “SELECT P”. Due to the changed
full-scale range Q

100%

, the output frequency (F) of the pulse output will be over- or undershot:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see Sect. 5.7 pulse output B1, Fct. 1.06.

5.2 Time constant

Fct. 1.02 TIMECONST.
Press

key.

Choice

ALL

(applies to display and all outputs)

ONLY I

(applies only to display, current and status output)

Select with

.

Transfer to number setting with

key. 1st number (cursor) flashes.

Set numerical value

0.2 - 99.9 Sec

(seconds)

Change flashing number (cursor) with the

key.

Use

key to shift cursor 1 place to right.

Press

key to return to Fct. 1.02 TIMECONST.